Unsatisfactory EICR - High resistance reading recorded at socket outlet identified for further investigation

Remedial work following unsatisfactory EICR

EICR Remedial Work

After an unsatisfactory Electrical Installation Condition Report (EICR) at a property in Hampton, Bring it Ohm Electrical Solutions carried out remedial work to investigate a high resistance fault on the downstairs socket circuit.

The fault was on the live conductor. My testing gave an initial resistance reading of 37.6 ohms, so I needed to investigate further to find and correct the poor connections.

What an Unsatisfactory EICR Means

An EICR records the condition of a property’s fixed electrical installation after it has been inspected and tested against BS 7671, the UK wiring regulations. The electrician gives each defect a code. C1 means danger is present, C2 means the defect is potentially dangerous, C3 means an improvement is recommended and FI means further investigation is needed.

A report is unsatisfactory when it records any C1, C2 or FI observation. The defects listed then need remedial work to put them right. Landlords in England must have the electrics in their rented properties checked at least every five years. Homeowners are generally recommended to arrange an EICR every 10 years or when the occupancy changes, and my guide on how to improve electrical safety at home covers other checks you can make.

Safely Isolating and Testing the Circuit

I started at the consumer unit. I safely isolated the circuit, then disconnected its conductors so I could test them.

Once I had confirmed the high resistance reading, I worked around the downstairs socket outlets in turn. At each one, I inspected the terminations and tested again to narrow down where the fault was.

Testing a downstairs socket circuit at the consumer unit in Hampton, showing an initial reading of 37.6 ohms
From this job: testing at the consumer unit, showing the initial reading of 37.6 ohms.

Identifying Loose Connections

Several socket outlets had loose connections. At one, the live conductor was so poorly secured that it came out of its terminal as I withdrew the socket from the wall.

I re-terminated and tightened the connection correctly, then tested the circuit again. The resistance reading dropped to approximately 19.3 ohms.

Remedial work following an unsatisfactory EICR in Hampton, beginning to bring the high resistance reading down
From this job: beginning to bring the high resistance reading down.

This was an improvement, but the reading showed that the circuit still needed further investigation.

Tracing the Remaining Faults

I carried on inspecting and testing the circuit. I checked a further three to four socket outlets and corrected more loose terminations along the way.

After these repairs, the resistance reading fell to 0.58 ohms. This is consistent with the expected result for this circuit and confirmed that the high resistance fault had been resolved.

Stage of investigationResistance reading
Initial test37.6 Ω
After correcting the loose live connection at one socketApproximately 19.3 Ω
After correcting the remaining loose connections0.58 Ω
Final testing of a downstairs socket circuit in Hampton, showing a corrected reading of 0.58 ohms
From this job: final testing, showing the corrected reading of 0.58 ohms.

The Result

Tracing the fault methodically allowed me to find and correct several poor connections on the downstairs socket circuit.

The final test confirmed that this EICR defect had been put right. The job also showed why I test again after each repair. Correcting one loose connection lowered the reading, but there were still other faults on the circuit to find.

This job was in Hampton, and if you live nearby on the Surrey side of the river, you can read more about my work as an electrician in Thames Ditton. I’m Paul, an electrician from Weybridge, and I also carry out EICR remedial work in Walton-on-Thames and Esher.